Analog Accessories


 
FLM-325-I4-A Contact Monitors
  • Monitors Normally Open (NO) or Normally Closed (NC) contacts
  • Monitored Normally Closed (NC) contacts can be configured with or without EOL resistor
  • Module address programming with the D5070 Analog Device Programmer
  • Bi‑colored LED provides module status
  • Digital data communications and power over a two‑wire circuit
  • EEPROM addressing
 
 
FLM-325-2R4-A Dual Relay Modules
  • Two independently configurable Form C contacts
  • Contacts are rated 1 A at 30 VDC or 0.5 A at 125 VAC
  • Module address programming with the D5070 Analog Device Programmer
  • Bi‑colored LED provides module status
  • Digital data communications and power over a two‑wire circuit
 
 
FLM-325-NA4 Supervised Output Modules
  • Contacts are rated 2 A at 24 VDC
  • Flexible application and quick response to emergency conditions
  • Can be alarmed or reset by zone or by individual address
  • Module address programming with the D5070 Analog Device Programmer
  • Bi‑colored LED provides module status
  • Digital data communications and power over a four‑wire circuit
 
 
FLM‑325‑N4 Supervised Output Module
  • Programmable evacuation tones of 4 s with a granularity of 250 ms
  • Contacts are rated 2 A at 30 VDC
  • Flexible application and quick response to emergency conditions
  • Can be alarmed or reset by zone or by individual address
  • Module address programming with the D5070 Analog Device Programmer between 1‑127
  • Bi‑colored LED provides module status
  • Digital data communications and power over a four‑wire circuit
 
 
D7035 Octal Relay Modules
  • Eight Form C programmable relay outputs
  • D7035 mounts conveniently inside the FACP enclosure; no separate enclosure needed
  • D7035B includes mounting skirt and enclosure for mounting outside of the FACP enclosure
  • Up to two modules are supported by the FACP
 
 
FPE‑1000‑NE Networking Card 3‑Ethernet
  • Provides three Ethernet ports using CAT 5 or better cable
  • Uses simple plug-in connection to the FPA‑1000‑V2
  • Connects as either Class A or Class B
  • Uses standard RJ45 connections
  • Provides second power input port for normal network operation during maintenance
 
 
FPE‑1000‑NW Networking Card 1‑Ethernet 2‑Wired
  • Provides media type change through RJ45 and wired connections
  • Provides one Ethernet port using CAT 5 or better cable
  • Uses simple plug-in connection to the FPA‑1000‑V2
  • Connects as either Class A or Class B
  • Provides second power input port for normal network operation during maintenance
 
 
FLM‑325‑IM Contact Module
  • Digital data communications and power provided over a two-wire circuit
  • Class B circuit for dry contact devices
  • Module address programming (1-254) with the D5070 Analog Device Programmer
 
 
Intelligent IP video solutions