- Home
- Aktuelle Seite Catalog
We will relaunch the website to offer you an improved user experience. Please keep in mind to update your bookmark after go-live.
Power provided via the SLC loop. | |
Current DrawAlarmStandbyWhen polled | 5 mA0.17 mA22 mA ± 20% |
Voltage (operating) | 24 VDC to 41 VDC |
Maximum allowable line resistance | 50 Ω maximum |
Protection category | IP 42 |
Relative Humidity | < 95% (non‑condensing) |
Installation temperature | +32°F to +100°F (0°C to +38°C) |
Storage temperature | -13°F to +176°F (-25°C to +80°C) |
Dimensions | |
Dimensions (diameter x height) | 4.4 in. x 2.0 in. (11.2 cm x 5.1 cm) |
Housing Material | CYCOLOY/ABS |
Airflow | 4000 ft./min (20 m/s) maximum |
Sensitivity (smoke sensor) | 1.25%/ft. to 3.5%/ft. (4.1%/m to 11.48%/m) |